EFAP-S752 |
750W Output Power
Supports Tylersburg Platform
Single +12V Output Rail
EPS2U Application for Rack Mount System
Dimensions: 100(W) x 70(H) x 239.5(D) mm |
 |
|
Features : |
| |
Universal Power Input
Active Power Factor Correction
Single +12V Output Rail
Remote DC Sense on +5V and +3.3V
Short Circuit Protection
Over Current Protection
Over Voltage Protection
MTBF >100,000 Hours |
General Specifications : |
| |
Input Range : 100 to 240 VAC, +/-10%
Power Factor: , ≧0.97 minimum at full load
Efficiency: ≧80%
Hold up Time: 17mS minimum, at 80% of maximum load
PSON (Remote ON/OFF): TTL compatible signal
Power Good: 100 to 500 ms, TTL compatible signal
Operating Temperature: 0 to 50 ℃
Operating Humidity: 20 to 90 % |
Regulation, Ripple & Noise: |
| |
|
Output
|
+3.3V
|
+5V
|
+12V
|
-5V
|
-12V
|
+5Vsb
|
|
Load Regulation
|
± 5%
|
± 5%
|
± 5%
|
|
± 10%
|
± 5%
|
|
Cross Regulation
|
± 5%
|
± 5%
|
± 5%
|
|
± 10%
|
± 5%
|
|
Line Regulation
|
± 1%
|
± 1%
|
± 1%
|
|
± 1%
|
± 1%
|
|
Ripple & Noise
|
50mV
|
60mV
|
120mV
|
|
120mV
|
50mV
|
|
Input and Output Ratings: |
| |
|
Input
|
Output
|
|
Voltage
|
Frequency
|
Current
|
Watt
|
Load
|
+3.3V
|
+5V
|
+12V
|
-5V
|
-12V
|
+5Vsb
|
|
100-240Vac
|
47-63Hz
|
10~4.5A
|
750W
|
Max. Load
|
26A
|
26A
|
60A
|
|
0.5A
|
3A
|
|
Min. Load
|
0.5A
|
0.5A
|
1A
|
|
0.1A
|
0A
|
|
|
NOTE:
- The +5 & +3.3 Volt combine total output shall not exceed 150W
- The +5, +3.3 and +12 Volt combine total output shall not exceed 732W
- Noise bandwidth is from DC to 20 MHz.
|
Agency Requirements : |
| |
Harmonic: Meet EN6 1000-3-2 standards
EMI/RFI: CE, FCC class B and CISPR class B
Safety: UL, cUL, CB, TUV, CCC |
|