EFRD-S2257H |
1U 250W DC To DC Redundant Power Supply
N+1 Redundant Configuration
Dimension: 106(W) x 41.5(H) x 260(D) mm |
|
|
Features : |
| |
N+1 Redundant Design
High Efficiency≥80%
Power Failure Alarm
Front Access Ability
0~50℃ Working Temperature |
General Specifications : |
| |
Input Range: -36V to -72VDC
Efficiency: ≧80% @ -48VDC
Short Circuit Protection
Over Current Protection
Over Voltage Protection
No load Operation
Over Temperature Protection
MTBF >100,000 Hours@25℃
Operating Temperature: 0 to 50 ℃
Operating Humidity: 20 to 90 %
EMI/RFI: CE, FCC class A
Safety: UL, CB, TUV, CCC, BSMI |
Regulation, Ripple & Noise: |
| |
|
Output
|
+3.3V
|
+5V
|
+12V
|
-12V
|
+5Vsb
|
|
Load Regulation
|
± 5%
|
± 5%
|
± 5%
|
± 5%
|
± 5%
|
|
Line Regulation
|
± 1%
|
± 1%
|
± 1%
|
± 1%
|
± 1%
|
|
Ripple & Noise
|
60mV
|
60mV
|
120mV
|
120mV
|
60mV
|
|
Input and Output Ratings: |
| |
|
Input
|
Output
|
|
Voltage
|
Current
|
Load
|
+3.3V
|
+5V
|
+12V
|
-12V
|
-5V
|
+5Vsb
|
|
-36V~ -72VDC
|
4-2A
|
Max. Load
|
20A
|
20A
|
20A
|
0.5A
|
-
|
2A
|
| Min. Load |
0A
|
0A
|
0.5A
|
0A
|
-
|
0A
|
|
|
NOTE:
- The +3.3 &+5 Volt total outputs shall not exceed 120W.
- Noise bandwidth is from DC to 20 MHz
|
|