EFRD-S257 |
250W ERP1U DC To DC Redundant Power Module
Dimension: 50.5(W) x 40(H) x 220(D) mm |
 |
|
Features : |
| |
High Efficiency≧80%
ERP1U Power Module Form Factor
N+1 Redundancy with Load Sharing Capability
0~50℃ Working Temperature |
General Specifications : |
| |
Efficiency: ≥80% at typical load
Short Circuit Protection
Over Current Protection
Over Voltage Protection
Over Temperature Protection
No Load Operation
MTBF >100,000 Hours
Operating Temperature: 0 to 50℃
Operating Humidity: 20 to 90 %
EMI/RFI: CE, FCC class A
Safety: UL, TUV, CCC, CB, BSMI |
Regulation, Ripple & Noise: |
| |
|
Output
|
+12V
|
-12V
|
+5Vsb
|
|
Load Regulation
|
± 5%
|
± 10%
|
± 5%
|
|
Line Regulation
|
± 1%
|
± 1%
|
± 1%
|
|
Ripple & Noise
|
120mV
|
120mV
|
60mV
|
|
Input and Output Ratings: |
| |
|
Input
|
Output
|
|
Voltage
|
Current
|
Load
|
+12V |
-12V |
+5Vsb
|
|
-36V~ -72VDC
|
9-4.5A
|
Max. Load
|
20A |
0.5A |
2A
|
| Min. Load |
0.8A |
0A |
0A
|
|
|
NOTE:
- Noise bandwidth is from DC to 20 MHz.
|
|